613-001760 Rev. AAT-DC2552XSL2 Data Center SwitchInstallation Guide
Tables10
11PrefaceThis guide contains instructions on how to install the AT-DC2552XS L2 Data Center Switch and the associated power supply and fan modules on a
Preface12Document ConventionsThis document uses the following conventions:NoteNotes provide additional information.CautionCautions inform you that per
Stack Installation Guide for AT-2552XS L2 Data Center Switch13Contacting Allied TelesisIf you need assistance with this product, you may contact Allie
Preface14
15Chapter 1OverviewThis chapter contains the following sections: “AT-DC2552XS Features” on page 16 “LEDs” on page 23 “Console Port” on page 29 “AT
Chapter 1: Overview16AT-DC2552XS FeaturesThe AT-DC2552XS L2 Data Center Switch has a high-density switching fabric (1280 Gbps) in a compact 1 RU chass
Stack Installation Guide for AT-2552XS L2 Data Center Switch17Installation OptionsThe AT-DC2552XS L2 Data Center Switch is designed to be installed in
Chapter 1: Overview18Optional QSFP+ TransceiversThe following QSFP+ transceivers direct attach cable assemblies have been approved by Allied Telesis a
Stack Installation Guide for AT-2552XS L2 Data Center Switch19AT-DC2552XSPhysicalDescriptionThe AT-DC2552XS L2 Data Center Switch physical description
Copyright © 2013 Allied Telesis, Inc.All rights reserved. No part of this publication may be reproduced without prior written permission from Allied T
Chapter 1: Overview20NoteThe AT-PWR06 power supply module is sold and packaged separately from the AT-DC2552XS L2 Data Center Switch. The fan module
Stack Installation Guide for AT-2552XS L2 Data Center Switch21WarningKeep the exhaust air vents clear of any obstructions to insure proper cooling of
Chapter 1: Overview22“Power/Fault LED” on page 25 for the functional description. Console Port - The console port is a standard RS-232 interface usin
Stack Installation Guide for AT-2552XS L2 Data Center Switch23LEDsHere are the descriptions of the switch’s LEDs.SFP+ Slot LED Each SFP+ slot has one
Chapter 1: Overview24QSFP+ Slot LEDs Each QSFP+ port has one link/activity LED labeled LINK/ACT. These LEDs are shown in Figure 4.Figure 4. QSFP+ LEDs
Stack Installation Guide for AT-2552XS L2 Data Center Switch25Power/Fault LED The Power/Fault LED are shown in Figure 5.Figure 5. Power/Fault LEDsThe
Chapter 1: Overview26NET MGMTLEDThe NET MGMT LED are shown in Figure 6.Figure 6. NET MGMT LEDsThe NET MGMT LEDs are described in Table 5.LINKLEDACTLED
Stack Installation Guide for AT-2552XS L2 Data Center Switch27FAN Status LEDs The fan status LEDs are shown in Figure 7.Figure 7. FAN Status LEDsThe f
Chapter 1: Overview28AC Power LED Each AT-PWR06 power supply module has a AC power (AC OK) LED. This LED is shown in Figure 8.Figure 8. AC Power LEDTh
Stack Installation Guide for AT-2552XS L2 Data Center Switch29Console PortThe Console port is used to locally configure the features and parameter set
3Electrical Safety and Emissions StandardsThis product meets the following standards.RFI Emissions FCC Class A, EN55022 Class A, CISPR 22 Class A, VCC
Chapter 1: Overview30AT-PWR06 Power Supply ModuleThe AT-DC2552XS L2 Data Center Switch is powered by one AT-PWR06 power supply module. A second AT-PWR
Stack Installation Guide for AT-2552XS L2 Data Center Switch31The components of the AT-PWR06 power supply module (refer to Figure 9 on page 30) are as
Chapter 1: Overview32AT-FAN06 Fan ModuleInstallation of two AT-FAN06 fan modules are required in the AT-DC2552XS. Each AT-FAN06 fan module is equipped
33Chapter 2Beginning the InstallationThe chapter contains the following sections: “Installation Overview” on page 34 “Reviewing Safety Precautions”
Chapter 2: Beginning the Installation34Installation OverviewTable 8 lists the installation procedures for the AT-DC2552XS L2 Data Center Switch. The p
Stack Installation Guide for AT-2552XS L2 Data Center Switch35Reviewing Safety PrecautionsPlease review the following safety precautions before you be
Chapter 2: Beginning the Installation36WarningClass I Equipment. This equipment must be earthed. The power plug must be connected to a properly wired
Stack Installation Guide for AT-2552XS L2 Data Center Switch37CautionRisk of explosion if battery is replaced by an incorrect type. Replace only with
Chapter 2: Beginning the Installation38WarningReliable earthing of rack-mounted equipment should be maintained. Particular attention should be given t
Stack Installation Guide for AT-2552XS L2 Data Center Switch39Planning the InstallationThe AT-DC2552XS L2 Data Center Switch can be installed on a des
4Translated Safety StatementsImportant: The indicates that translations of the safety statement are available in the PDF document “Translated Safety
Chapter 2: Beginning the Installation40Unpacking the SwitchRefer to the following figures in this section to verify the contents of the shipping conta
Stack Installation Guide for AT-2552XS L2 Data Center Switch41AT-PWR06Power SupplyThe contents of the AT-PWR06 power supply module shipping box are li
Chapter 2: Beginning the Installation42AT-FAN06 FanModuleThe contents of the AT-FAN06 fan module shipping box are listed in Figure 12.Figure 13. Conte
43Chapter 3Installing the Switch and ModulesYou may install the AT-DC2552XS Switch on a desktop or in a standard 19 inch equipment rack. In addition,
Chapter 3: Installing the Switch and Modules44Installing the Switch on a DesktopTo install the switch on a desktop, perform the following procedure:No
Stack Installation Guide for AT-2552XS L2 Data Center Switch45Installing the Switch in an Equipment RackNoteTo install the switch on a desktop, refer
Chapter 3: Installing the Switch and Modules46This procedure requires the following items: Eight bracket screws (included with the switch) Two equip
Stack Installation Guide for AT-2552XS L2 Data Center Switch472. Have another person hold the switch in the equipment rack while you secure it using s
Chapter 3: Installing the Switch and Modules48Installing and Replacing AT-PWR06 Power Supply ModuleThe AT-PWR06 power supply module may be installed i
Stack Installation Guide for AT-2552XS L2 Data Center Switch49CautionThe PSU blank cover should be installed if an AT-PWR06 power sup-ply module is no
5Preface...
Chapter 3: Installing the Switch and Modules505. Tighten the captive screws to fasten of the power supply module to the chassis. See Figure 20.Figure
Stack Installation Guide for AT-2552XS L2 Data Center Switch51NoteIf a new AT-PWR06 power supply module is not available to replace the module you are
Chapter 3: Installing the Switch and Modules52Installing and Replacing AT-FAN06 Fan ModuleThe following procedures are included in this section: “Ins
Stack Installation Guide for AT-2552XS L2 Data Center Switch534. Tighten the captive screws to fasten the fan module to the chassis. See Figure 23.Fig
Chapter 3: Installing the Switch and Modules54Replacing FanModuleThe AT-FAN06 fan module is hot swappable within the chassis. The power to the chassis
55Chapter 4Installing the SFP+ and QSFP+ Transceivers and CablesThe list of approved SFP+ and QSFP+ transceivers and direct connect cables that may be
Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables56Installing SFP+ Transceivers and CablesGeneralGuidelinesReview the following guideli
Stack Installation Guide for AT-2552XS L2 Data Center Switch57Installing SFP+TransceiverPerform the following procedure to install a SFP+ transceiver:
Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables58Figure 26. Installing a SFP+ TransceiverNoteIf you are ready to attach the fiber opt
Stack Installation Guide for AT-2552XS L2 Data Center Switch597. Refer to Table 9 on page 56 for the recommended fiber optic cable. Insert the cable t
Contents6Chapter 6: Managing the Switch ...
Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables602. Remove the SFP+ direct attach cable from its shipping container and store the pac
Stack Installation Guide for AT-2552XS L2 Data Center Switch61Installing QSFP+ Transceivers and CablesReview the following guidelines before installin
Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables62Figure 31. Removing QSFP+ Slot Dust Cover3. If you are installing the transceiver in
Stack Installation Guide for AT-2552XS L2 Data Center Switch63Figure 33. Removing QSFP+ Dust Cover7. Insert the fiber optic cable to the port on the t
Chapter 4: Installing the SFP+ and QSFP+ Transceivers and Cables64Figure 35. Removing QSFP+ Slot Dust Cover3. If you are installing the QSFP+ MTHTP ca
65Chapter 5Powering the SwitchThe procedures in this chapter are listed here: “Powering On the Switch” on page 66 “Turn Off the switch” on page 68
Chapter 5: Powering the Switch66Powering On the SwitchThe power turns on automatically when you connect the power cable to one or both of the AT-PWR06
Stack Installation Guide for AT-2552XS L2 Data Center Switch676. The next step in the installation process is to access the AT-DC2552XS management int
Chapter 5: Powering the Switch68Turn Off the switchTo turn off the AC power to the switch, perform the following procedure.WarningPower cord is used a
69Chapter 6Managing the SwitchYou may manage an AT-DC2552XS L2 Data Center Switch with these methods and tools: Local management via Telnet client R
7Figure 1: AT-DC2552XS Front Panel View ...
Chapter 6: Managing the Switch70Local ManagementYou can manage the AT-DC2552XS switch locally through the Console port (USB connector) the rear panel
Stack Installation Guide for AT-2552XS L2 Data Center Switch71 Stop bits: 1 Flow control: None NoteThe port settings are for a DEC VT100 or ANSI ter
Chapter 6: Managing the Switch72Remote Network Management You can manage the AT-DC2552XS switch remotely through any of the Ethernet ports (1 through
Stack Installation Guide for AT-2552XS L2 Data Center Switch73Figure 38. Connecting the Twisted Pair Cable into the NET MGMT port3. With the AT-DC2552
Chapter 6: Managing the Switch74
75Chapter 7TroubleshootingThis chapter contains suggestions on how to troubleshoot the switch if a problem occurs.NoteFor further assistance, please c
Chapter 7: Troubleshooting76 Verify that the operating specifications of the fiber optic ports on the SFP+ transceiver and the remote network device
Stack Installation Guide for AT-2552XS L2 Data Center Switch77 If the remote network device is a managed device, use its management firmware to deter
Chapter 7: Troubleshooting78
79Appendix ATechnical SpecificationsThis appendix contains the technical specifications for the AT-DC2552XS L2 Data Center Switch.Physical Specificati
Figures8
Appendix A: Technical Specifications80Power SpecificationsAT-PWR06 Input SpecificationsCertificationsQuality and ReliabilityTable 14. AT-PWR06 Input
Stack Installation Guide for AT-2552XS L2 Data Center Switch81RJ-45 Twisted Pair Port PinoutsFigure 39 illustrates the pin layout of an RJ-45 connecto
Appendix A: Technical Specifications82Table 18 lists the pin signals when a port operating at 1000 Mbps.Table 18. Pin Signals - 1000 MbpsPinout Pair
Stack Installation Guide for AT-2552XS L2 Data Center Switch83
Appendix A: Technical Specifications84
9TablesTable 1: Twisted Pair Cable Specifications for the NET MGMT Port ...................